Not a direct fit. Joining 3 inch camlock coupling to 3" NH fire hose thread (NST) needs a 3 inch camlock to 3-6NH threaded adapter. Sealing method, the real-world trap, and the exact part to use.

Updated 05 September 2026.

Connect 3 inch camlock coupling to 3" NH fire hose thread (NST)

How to join 3" camlock (A-A-59326) and 3-6NH, and what stops it leaking.

Needs adapter
End A
3 inch camlock coupling (3" camlock (A-A-59326))
Seals on its coupling
via adapter
End B
3" NH fire hose thread (NST) (3-6NH)
Seals on rubber gasket in the female swivel
Adapter needed3 inch camlock to 3-6NH threaded adapter

Not a direct fit. Joining 3 inch camlock coupling to 3" NH fire hose thread (NST) needs a 3 inch camlock to 3-6NH threaded adapter.

The part to buy

A 3 inch cam-and-groove coupling has no thread of its own, so it reaches a 3-6NH (NH fire hose) port through a same-size threaded camlock adapter: a Type A male adapter or a threaded coupler carrying the 3-6NH thread on its back. That thread is a straight (parallel), 60 degree form of 92.02 mm major diameter at 6 threads per inch and seals rubber gasket in the female swivel; the cam end then mates to its opposite 3 inch camlock half.

The 3 inch cam profile and the 3-6NH thread are two separate choices. A correct 3-6NH back thread still leaves you with the wrong front if the half you mate to is not the matching 3 inch cam type, so confirm both the size and the A-to-F type before buying.